PSC deficiency code 07105: Fire doors/openings in fire-resisting divisions

Area 07 Fire safety

This code covers the doors, hatches and other openings that sit in fire-resisting bulkheads and decks: accommodation stairway enclosures, galley and engine room boundaries, control station doors. A fire door only holds a fire back if it closes by itself and seals, and that is what the inspector tests.

What the inspector looks at

The inspector walks the accommodation and engine casing and tries a few doors:

  • Does the door close fully and latch from any opening angle, without a push?
  • Are hold-back devices of an approved type with release from the control station, where fitted, and are there no hooks, wedges or ropes holding self-closing doors open?
  • Are seals, gaskets and the door frame intact, with no gaps, holes or cut-outs for cables?
  • Do door closers work, or are they disconnected, leaking or missing arms?
  • Have non-approved items been fitted, such as ventilation grilles cut into A-class doors or replacement doors of an unknown standard?

Common findings

  • Self-closing fire door to engine room held open with a wedge
  • Fire door does not close fully, closer defective
  • Door closing device removed or disconnected
  • Fire door seal damaged or missing
  • Holes in fire door or frame for cables or pipes not sealed with approved penetration
  • Fire door to galley/stairway enclosure jammed, unable to latch

The rule behind it

SOLAS Chapter II-2, Regulation 9 (containment of fire) sets the requirements for fire doors and openings in A and B class divisions, including self-closing arrangements and hold-back devices. The fire test standards for the doors themselves are in the FTP Code. SOLAS II-2 Regulation 14 requires the fire protection systems to be kept in working order under the ship's maintenance plan, which is where missing or poor maintenance records come in.

Action codes you are likely to see

A wedged door that the crew removes on the spot is usually closed with code 10. A defective closer or a damaged seal tends to get 17 (rectify before departure) or 16 (within 14 days), depending on spares on board. Several doors in the same boundary that don't close, or a main stairway enclosure that can't be closed, can be raised as 30, because the fire boundary no longer holds. See the action taken codes.

How to close it

Repair or replace the closer, seals or hardware with parts that keep the door's approval. Any penetration added through the door or frame has to be made good with an approved system, and class should be consulted if the door itself was modified or replaced. Test every fire door in the area after the repair, record it in the planned maintenance system and keep photos and the record together with the Form B. The fire dampers in the same boundaries are often checked in the same round.

Questions

Is a fire door held open with a wedge a detainable deficiency?

On its own it is usually rectified on the spot, but it can count toward detention when combined with other fire boundary failures or when it shows the ship's maintenance and crew familiarity are not working.

Can we fit a hook to keep a fire door open in port?

Self-closing fire doors may only be held open by approved hold-back devices that release automatically or from a control station. A hook or rope is not an approved means and will be written up.

Do we need class when replacing a fire door?

The new door must be approved for the division it sits in, so involve class and keep the approval papers on board.

Sources

Written by the SuperRonin team from the sources above. Last updated 27 Oct 2026. This page explains the rules; the regulation, the PSC officer and your flag and class have the final word. If something here doesn't match what you see on board, write to [email protected] and we'll correct it.

Track each deficiency to closure

SuperRonin keeps your fleet's certificates, surveys and PSC inspections. Enter the deficiencies from Form B and one click turns each into a condition with the due date its action code gives, so the office sees what is open and the bell rings before the date. Free during the pilot.

Other codes in Fire safety

All deficiency codes · Action taken codes