LISCR FIR-001: Fire-Protection Systems and Appliances

Revised marine notice providing guidelines for maintenance and inspection of fire protection systems and appliances, prohibiting PFOS-containing extinguishing media effective 1 January 2026 and specifying that verification of tests is an integral part of annual statutory surveys to be satisfied by the attending classification society surveyor.

Issued by
Liberia Maritime Authority
Number
FIR-001
Date
23 Feb 2026
Applies to
all ships and mobile offshore units (MOUs), including MODUs
Refers to
SOLAS Chapter II-2, as amended, International Code for Fire Safety Systems (FSS Code), as amended, Resolution MSC.532(107), Resolution MSC.537(107), MSC.1/Circ.1312, MSC.1/Circ.1312/Corr.1, Marine Notice SAF-018, MARPOL Annex VI

Key points

  • Effective 1 January 2026, the use of fire extinguishing media containing perfluorooctane sulfonic acid (PFOS) is prohibited. Ships constructed before 1 January 2026 must comply not later than the first survey on or after 1 January 2026.
  • The verification of examinations and tests in Sections 1.2 through 1.6 is an integral part of the annual statutory surveys for the SOLAS Safety Equipment Certificate; inspection and verification of items in Sections 1.2 through 1.7 must be to the satisfaction of the attending classification society surveyor.
  • For fixed CO2 systems, high pressure and pilot cylinders must be weighed or verified biennially (intervals of 2 years ± 3 months) in passenger ships or at each intermediate, periodical or renewal survey in cargo ships to confirm the charge is above 90% of nominal; cylinders below 90% must be refilled. Hydrostatic testing follows schedules based on vessel age, with 10% tested at the 10-year anniversary and all cylinders tested before the 20-year anniversary and every 10 years thereafter for new ships.
  • Existing Halon systems may continue in use with no phase-out date, but new installations are prohibited. The Administration may authorize a five-year extension of the 20-year hydrostatic testing requirement in writing, subject to conditions including content verification, visual inspection, and ultrasonic thickness gauging.
  • Ships constructed on or after 1 July 2014 must carry a minimum of two two-way portable radiotelephone apparatus for each fire party, certified safe type for zone 1 hazardous areas; each fire party must have at least two explosion-proof or intrinsically safe radios dedicated only for fire party use.

Key points by AI from the PDF, with page numbers. Read the original before acting.

Earlier and later documents

  • Replaces Marine Notice FIR-001, dated 01/26

Get new LISCR documents in your bell and inbox

SuperRonin keeps your fleet's certificates and surveys, and sends each new circular of your vessels' flag, class and P&I club as one line with a link. Free during the pilot.

More from LISCR

All LISCR documents · All issuers we follow